IS-AIN8 unit can be mounted on DIN rail (35mm).
5.3.7. IGL-RA15 Remote annunciator
Remote (CAN bus, up to 200 meters) 15 LED states indicator. IGL-RA15 unit can be connected
to controller via CAN as Binary output group with addresses 1+2 or 3+4 or 5+6 or 7+8.
To configure IGL-RA15 use GenConfig -> Modules -> Available modules, select IGL-RA15
module and add it using Insert button. GenConfig automatically adds IGL-RA15 binary outputs
to the configuration.
For more information about IGL-RA15 consult manual (IGL-RA15-2.0.pdf) and New features