EasyManuals Logo

ComAp IS-NTC-BB Installation Guide

ComAp IS-NTC-BB
149 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #144 background imageLoading...
Page #144 background image
IGS-NT Installation Guide
144
20.12.3. Analog inputs
Not electrically separated
Number of inputs 4
Resolution 10 bits
Maximal resistance range 0 250
Maximal voltage range 0 100 mV
Maximal current range 0 20 mA
Resistance measurement tolerance 1 % 2 out of measured value
Voltage measurement tolerance 1,5 % 1mV out of measured value
Current measurement tolerance 2,5 % 0,5mA out of measured value
20.12.4. Analog output
Not electrically separated
Number of inputs 1
Resolution 10 bits
Output range 0 to 20 mA ± 0,33 mA
20.13. IS-AIN8
Nominal power supply 24 VDC
Power supply range 8 36 VDC
Max. consumption 250 mA
Mechanical dimensions: 150 x 160 x 50 mm ,
DIN rail (35 mm) mounted
Connection to controller (galvanically separated) CAN1
Operating temperature -40..+70
o
C
Storage temperature -40..+80
o
C
Protection front panel IP 20
Humidity 95% without condensation
Standard conformity
Low Voltage Directive EN 61010-1:95 +A1:97
Electromagnetic Compatibility EN 50081-1:94 (EN 61000-6-3)
EN 50081-2:96 (EN 61000-6-4)
EN 50082-1:99 (EN 61000-6-1)
EN 50082-2:97 (EN 61000-6-2)
20.13.1. Analog inputs
Nominal power supply 24 VDC
Power supply range 8 36 VDC
Number of inputs 8
Not galvanic separated
Resolution 16 bits

Table of Contents

Other manuals for ComAp IS-NTC-BB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp IS-NTC-BB and is the answer not in the manual?

ComAp IS-NTC-BB Specifications

General IconGeneral
BrandComAp
ModelIS-NTC-BB
CategoryController
LanguageEnglish

Related product manuals