27Condair CDC, CDC-NA, CDC-ST and CDC-SL
3. Only for CDC: Set the output signal of the CDC to "0-10V" using the Jumpers JP1 and JP3 on the
control board of the CDC.
Note: other output signal settings (e.g. 4-20mA) are also possible, see CDC jumper settings in Sec-
tion 2.7.
4. Set the Condair RS/RS OC into operation, go to the control menu of the unit software and set the
parameters "Source" to "Analog", "Control Mode CH 1" to "RH PI", "Signal Type Control CH 1"
to "0-10V" (or to output signal set on CDC) or "2-10V" (for CDC-NA) and the parameters "Setpoint
Channel 1", "Band Channel 1" and "ITime Channel 1" to the desired values (refer to the Condair
RS operation manual).
Note: if required, also set the limitation parameters (signal Y2). In order to be able to set these
parameters, the "Control channels" parameter must be set to "Double" (refer to the Condair RS
operation manual).