45Condair CRC and CRC-NA
4. Set the Condair RS/RS OC into operation, go to the control menu of the unit software and set the
parameters "Source" to "Analog", "Control Mode CH 1" to "RH PI", "Signal Type Control CH 1"
to "0-10V" (or to output signal set on CRC) or "2-10V" (for CRC-NA) and the parameters "Setpoint
Channel 1", "Band Channel 1" and "ITime Channel 1" to the desired values (refer to the Condair
RS operation manual).