Product Manual – DOC. 8879C DM-NVX-36x(C) Encoders/Decoders • 65
On the LEX device, the <UsbRemoteDeviceId_F> and
<UsbRemoteDeviceId2_F> through <UsbRemoteDeviceId7_F> serial
output joins report the MAC address of each REX device to which the
LEX device is to be paired.
• For Layer 3 transport:
• Copy the IP address (UsbLocalDeviceIpAddress) of the LEX device into
the
<UsbRemoteDeviceIpAddress> serial input join on the REX device.
On the REX device, the <UsbRemoteDeviceIpAddress_F> serial output join
reports the IP address of the LEX device to which the REX device is to be
paired.
• Copy the IP address (UsbLocalDeviceIpAddress) of the REX device into
the
<UsbRemoteDeviceIpAddress> serial input join on the LEX device.
On the LEX device, the <UsbRemoteDeviceIpAddress_F> serial output join
reports the IP address of the REX device to which the LEX device is to be
paired.
5. Do either of the following:
• Trigger the <Pair> digital input join on all DM NVX devices (LEX and REX).
• Trigger the <AutomaticUSBPairingEnabled> digital input join on all DM NVX
devices (LEX and REX).
To remove pairing between DM NVX devices, do either of the following:
• If automatic USB pairing is not enabled, trigger the <RemovePairing> digital
input join on each DM NVX device.
• If automatic USB pairing is enabled, do either of the following:
- For Layer 2, enter 00:00:00:00:00:00 or an empty string into the
<UsbRemoteDeviceId> serial input join.
- For Layer 3, enter an unused IP address into the
<UsbRemoteDeviceIpAddress> serial input join.
For additional information about configuration of USB routing, refer to the SIMPL
Windows help file.