Curtis PMC 1297 Manual
46
B. HYDRAULIC PARAMETERS
The various hydraulic parameters adjust the hydraulic systems operating character-
isticsits acceleration, speed, and responsiveness. These parameters allow the hy-
draulic system to be tailored to a specific application, or to a specific operators
preferences.
The 1297 controls the speed of the pump motor, and also the valves on the Lift
cylinders hydraulic line. By so doing, it controls the hydraulic path for Lift and
Lower operations. The hydraulic path for any other hydraulic operationse.g.,
reach, tilt, sideshift, rotateis provided by the vehicle manufacturer, with the 1297
controlling the pump motor speed but not the hydraulic path itself.
PUMP C/L
The pump current limit parameter denes the maximum pump motor arma-
ture current. The pump current limit is adjustable from 25 amps up to the
controllers full rated pump motor current. (The full rated pump current
depends on the controller model; see specications in Table E-1.)
PUMP MAX SPEED
When the Lift switch is closed, the controller activates the load-hold valve, thus
enabling the Lift functionas shown in Figure 20. The maximum pump speed
parameter denes the maximum allowed armature PWM output during Lift
operations. The maximum pump speed parameter is adjustable from 0% to
100% of full output.
The maximum pump speed is tuned as part of the vehicle performance
adjustment process (Section 5).
NO LOAD C/L
The no load pump current limit parameter sets the current that will dene the
no load state. When the pump current is below this ceiling, the pump is
considered to have no load, and the no load maximum pump speed will apply.
If a separate maximum speed is not desired for unloaded situations, the no load
pump current limit can be set at the same value as the regular pump current
limit. The no load pump current limit can be adjusted from 0 amps up to the
programmed pump current limit.
NO LOAD SPEED
The no load maximum pump speed parameter allows a higher maximum
pump speed to be in effect when the pump motor is operating below the set no
load current limit. The no load maximum pump speed parameter has the same
3
B
PROGRAMMABLE HYDRAULIC PARAMETERS: Pump