Installer reference guide
225
ERLA11~16D + EBBH/X11+16D
Daikin Altherma 3 R W
4P643603-1B – 2022.05
Compressor forced off
Compressor forced off mode can be activated to only allow the backup
heater to provide domestic hot water and space heating. When this mode is
activated:
Heat pump operation is NOT possible
Cooling is NOT possible
# Code Description
[9.5.2] [7-06] Activation of the Compressor forced off
mode:
0: disabled
1: enabled
Balancing
Priorities
For systems with a separate domestic hot water tank.
# Code Description
[9.6.1] [5-02] Space heating priority: Defines
whether domestic hot water is made by
booster heater only when outdoor
temperature is below space heating priority
temperature.
0: Off (default)
1: On
Please do NOT change the default value.
[5-01] Equilibrium temperature and [5-03]
Space heating priority temperature are related
to backup heater. So, you must set [5-03] equal
or a few degrees higher than [5-01].
[9.6.2] [5-03] Priority temperature: Defines the
outdoor temperature which below the
domestic hot water will be heated by booster
heater only.
Please do NOT change the default value.
Range: –15°C~35°C
[9.6.3] [5-04] Offset BSH setpoint: Setpoint correction
for domestic hot water temperature: setpoint
correction for the desired domestic hot water
temperature, to be applied at low outdoor
temperature when space heating priority is
enabled. The corrected (higher) setpoint will
make sure that the total heat capacity of the
water in the tank remains approximately
unchanged, by compensating for the colder
bottom water layer of the tank (because the
heat exchanger coil is not operational) with a
warmer top layer.
Range: 0°C~20°C