6 | Application guidelines
Installer reference guide
64
ERLA11~16D + EBBH/X11+16D
Daikin Altherma 3 R W
4P643603-1B – 2022.05
You can combine the BBR16 power limitation with the other kW power
consumption controls. If you do so, the unit uses the most restrictive control.
P
i
t
BBR16
a
b
P
i
Power input
t Time
BBR16 BBR16 limit level
a Power limitation active
b Actual power input
Setup and configuration
No additional equipment needed.
Set the power consumption control settings in [9.9] via the user interface (see
"Power consumption control"[4231]):
- Activate BBR16
- Set the desired power limitation level
6.6.5 Smart Grid capacity limitation due to buffering
Smart Grid limitation for buffering is only possible if a Smart Grid is installed and
Recommended on mode is active.
You can combine Recommended on mode capacity limitation with other power
consumption controls. If you do so, the unit uses the most restrictive control.
INFORMATION
In case Smart Grid Forced off mode is active, the outdoor unit compressor and
electrical heaters will NOT operate.
Setup and configuration
See "9.3.11 To connect a Smart Grid" [4 140] and "Benefit kWh power
supply"[4228].
6.7 Setting up an external temperature sensor
You can connect one external temperature sensor. It measures the indoor or
outdoor ambient temperature. We recommend to use an external temperature
sensor in the following cases: