7 | Unit installation
Installer reference guide
70
ERLA11~16D + EBBH/X11+16D
Daikin Altherma 3 R W
4P643603-1B – 2022.05
H1150
200
200
500
(mm)
≥450
H Height measured from the bottom of the casing to the floor
Additionally to the spacing guidelines: Because the total refrigerant charge in the
system is ≥1.84 kg, the room where you install the indoor unit must also comply
with the conditions described in "7.1.5Installation patterns"[472].
Do NOT install the unit in places such as:
In places where a mineral oil mist, spray or vapour may be present in the
atmosphere. Plastic parts may deteriorate and fall off or cause water leakage.
Sound sensitive areas (e.g. near a bedroom), so that the operation noise will
cause no trouble.
In places with high humidity (max. RH=85%), for example a bathroom.
In places where frost is possible. Ambient temperature around the indoor unit
must be >5°C.
7.1.4 Special requirements for R32 units
Additionally to the spacing guidelines: Because the total refrigerant charge in the
system is ≥1.84 kg, the room where you install the indoor unit must also comply
with the conditions described in "7.1.5Installation patterns"[472].
WARNING
Do NOT pierce or burn refrigerant cycle parts.
Do NOT use means to accelerate the defrosting process or to clean the
equipment, other than those recommended by the manufacturer.
Be aware that R32 refrigerant does NOT contain an odour.
WARNING
The appliance shall be stored so as to prevent mechanical damage and in a well-
ventilated room without continuously operating ignition sources (example: open
flames, an operating gas appliance or an operating electric heater) and have a room
size as specified below.
NOTICE
Do NOT re-use joints and copper gaskets which have been used already.
Joints made in installation between parts of refrigerant system shall be accessible
for maintenance purposes.