6 | Application guidelines
Installer reference guide
62
ERLA11~16D + EBBH/X11+16D
Daikin Altherma 3 R W
4P643603-1B – 2022.05
A Outdoor unit
B Indoor unit
C DHW tank
D Energy management system
a Power limitation activation (4 digital inputs)
b Backup heater
c Booster heater
P
i
t
DI4
DI3
DI1
a
b
P
i
Power input
t Time
DI Digital inputs (power limitation levels)
a Power limitation active
b Actual power input
Setup
Demand PCB (option EKRP1AHTA) needed.
Maximum four digital inputs are used to activate the corresponding power
limitation level:
- DI1 = strongest limitation (lowest energy consumption)
- DI4 = weakest limitation (highest energy consumption)
Specification of the digital inputs:
- DI1: S9S (limit 1)
- DI2: S8S (limit 2)
- DI3: S7S (limit 3)
- DI4: S6S (limit 4)
Refer to the wiring diagram for more information.
Configuration
Set the power consumption control settings in [9.9] via the user interface (for the
description of all settings, see "Power consumption control"[4231]):
- Select limitation by digital inputs.
- Select the type of limitation (power in kW or current in A).
- Set the desired power limitation level corresponding to each digital input.
INFORMATION
In case more than 1 digital input is closed (at the same time), the digital input priority
is fixed: DI4 priority>…>DI1.
6.6.3 Power limitation process
The outdoor unit has better efficiency than the electrical heaters. Therefore, the
electrical heaters are limited and turned OFF first. The system limits power
consumption in the following order:
1 Limits certain electrical heaters.