14.2 Yearly maintenance
14.2.1 Yearly maintenance outdoor unit: overview
Check the following at least once a year:
▪ Heat exchanger
14.2.2 Yearly maintenance outdoor unit: instructions
Heat exchanger
The heat exchanger of the outdoor unit can get blocked up due to dust, dirt,
leaves, etc. It is recommended to clean the heat exchanger yearly. A blocked heat
exchanger can lead to too low pressure or too high pressure leading to worse
performance.
14.2.3 Yearly maintenance indoor unit: overview
▪ Water pressure
▪ Magnetic filter/dirt separator
▪ Water pressure relief valve
▪ Pressure relief valve of the domestic hot water tank
▪ Switch box
▪ Booster heater of the domestic hot water tank
14.2.4 Yearly maintenance indoor unit: instructions
Water pressure
Keep water pressure above 1bar. If it is lower, add water.
Magnetic filter/dirt separator
a Screw connection
b Magnetic sleeve
c Drain valve
d Drain cap
The yearly maintenance of the magnetic filter/dirt separator consists of:
▪ Checking if both parts of the magnetic filter/dirt separator are still screwed
tight (a).
▪ Emptying the dirt separator as follows:
1 Take off the magnetic sleeve (b).
2 Unscrew the drain cap (d).
3 Connect a drain hose to the bottom of the water filter so that the water and
dirt can be collected in a suitable container (bottle, sink...).