6 | Application guidelines
Installer reference guide
41
ERLA11~16D + EBBH/X11+16D
Daikin Altherma 3 R W
4P643603-1B – 2022.05
Comfort. You can set the desired room temperature, including schedules, for
each room via the room thermostats.
Radiators – Multiple external room thermostats
Setup
A Main leaving water temperature zone
B Room 1
C Room 2
a External room thermostat
b Bypass valve
c Relay
For more information about connecting the electrical wiring to the unit, see:
- "9.2Connections to the outdoor unit"[4120]
- "9.3Connections to the indoor unit"[4123]
For each room, a shut-off valve (field supplied) is installed to avoid leaving water
supply when there is no heating or cooling demand.
A bypass valve must be installed to make water recirculation possible when all
shut-off valves are closed. To guarantee reliable operation, provide a minimum
water flow as described in table "To check the water volume and flow rate" in
"8.5Preparing water piping"[4106].
The user interface integrated in the indoor unit decides the space operation
mode. Mind that the operation mode on each room thermostat must be set to
match the indoor unit.
The room thermostats are connected to the shut-off valves. They are also
connected to the indoor unit (X2M/35 and X2M/30) -via a relay (field supplied)-
to give feedback when operation is needed. The indoor unit will supply leaving
water as soon as there is a request from one of the rooms.
Configuration
Setting Value
Unit temperature control:
#: [2.9]
Code: [C-07]
1 (External room thermostat):
Unit operation is decided by the
external thermostat.
Number of water temperature zones:
#: [4.4]
Code: [7-02]
0 (Single zone): Main