6 | Application guidelines
Installer reference guide
43
ERLA11~16D + EBBH/X11+16D
Daikin Altherma 3 R W
4P643603-1B – 2022.05
INFORMATION
To increase comfort and performance, we recommend to install the valve kit option
EKVKHPC on each heatpump convector.
Configuration
Setting Value
Unit temperature control:
#: [2.9]
Code: [C-07]
1 (External room thermostat):
Unit operation is decided by the
external thermostat.
Number of water temperature zones:
#: [4.4]
Code: [7-02]
0 (Single zone): Main
Benefits
Compared with heatpump convectors for one room:
Comfort. You can set the desired room temperature, including schedules, for
each room via the remote controller of the heatpump convectors.
Combination: Underfloor heating + Heatpump convectors – Multiple rooms
Setup
A Main leaving water temperature zone
B Room 1
C Room 2
a External room thermostat
b Heatpump convectors (+ controllers)
For more information about connecting the electrical wiring to the unit, see:
- "9.2Connections to the outdoor unit"[4120]
- "9.3Connections to the indoor unit"[4123]
For each room with heat pump convectors: The heat pump convectors are
directly connected to the indoor unit.