7 | Unit installation
Installer reference guide
77
ERLA11~16D + EBBH/X11+16D
Daikin Altherma 3 R W
4P643603-1B – 2022.05
Table 3: Maximum chimney length
When installing a chimney, the chimney length must be less than the maximum chimney length.
Use the columns with the correct refrigerant charge. For intermediate refrigerant charges, use the columns with
the higher value. Example: If the refrigerant charge is 4.0kg, use the columns of 5.8kg.
For intermediate diameters, use the column with the lower value. Example: If the diameter is 23mm, use the
column of 22mm.
X: Not allowed
Maximum chimney length (m) – In case of Refrigerant charge=3.8kg (and T=60°C) In case of Refrigerant charge=5.8kg (and T=60°C)
Chimney Inside diameter of chimney (mm) Inside diameter of chimney (mm)
20 22 24 26 28 20 22 24 26 28
Straight pipe 19.03 33.90 55.16 84.54 124.06 3.37 9.47 18.40 30.91 47.91
1× 90° elbow 17.23 31.92 53.00 82.20 121.54 1.57 7.49 16.24 28.57 45.39
2× 90° elbow 15.43 29.94 50.84 79.86 119.02 X 5.51 14.08 26.23 42.87
3× 90° elbow 13.63 27.96 48.68 77.52 116.50 X 3.53 11.92 23.89 40.35
Table 4: Minimum bottom opening area for natural ventilation
Take the following into account:
Use the correct table. For intermediate refrigerant charges, use the table with the higher value. Example: If the
refrigerant charge is 4.3kg, use the table of 4.8kg.
For intermediate floor areas, use the column with the lower value. Example: If the floor area is 12.50m², use the
column of 10.00m².
For intermediate release height values, use the row with the lower value. Example: If the release height is
2.20m, use the row of 2.1m.
A
nv
: Bottom opening area for natural ventilation.
A
nv-min
: Minimum bottom opening area for natural ventilation.
(*): Already OK (no ventilation openings needed).
A
nv-min
(dm²) – In case of Refrigerant charge=3.8kg
Release height (m) Floor area of room A (m²) [! NOT room A + room B !]
5.00 10.00 15.00 20.00 25.00 30.00 35.00
1.95 3.5 0.7 (*) (*) (*) (*) (*)
2.1 3.0 (*) (*) (*) (*) (*) (*)
2.25 2.5 (*) (*) (*) (*) (*) (*)
2.4 2.1 (*) (*) (*) (*) (*) (*)
2.55 1.7 (*) (*) (*) (*) (*) (*)
2.7 1.3 (*) (*) (*) (*) (*) (*)
2.85 1.0 (*) (*) (*) (*) (*) (*)
3 0.6 (*) (*) (*) (*) (*) (*)
A
nv-min
(dm²) – In case of Refrigerant charge=4.8kg
Release height (m) Floor area of room A (m²) [! NOT room A + room B !]
5.00 10.00 15.00 20.00 25.00 30.00 35.00
1.95 5.7 3.2 1.4 (*) (*) (*) (*)
2.1 5.2 2.5 0.4 (*) (*) (*) (*)
2.25 4.6 1.7 (*) (*) (*) (*) (*)
2.4 4.1 1.1 (*) (*) (*) (*) (*)
2.55 3.7 0.4 (*) (*) (*) (*) (*)
2.7 3.2 (*) (*) (*) (*) (*) (*)
2.85 2.8 (*) (*) (*) (*) (*) (*)
3 2.4 (*) (*) (*) (*) (*) (*)
A
nv-min
(dm²) – In case of Refrigerant charge=5.8kg
Release height (m) Floor area of room A (m²) [! NOT room A + room B !]
5.00 10.00 15.00 20.00 25.00 30.00 35.00
1.95 8.0 5.8 4.2 2.5 0.7 (*) (*)
2.1 7.3 4.9 3.1 1.3 (*) (*) (*)
2.25 6.7 4.1 2.1 0.1 (*) (*) (*)
2.4 6.1 3.3 1.2 (*) (*) (*) (*)
2.55 5.6 2.6 0.4 (*) (*) (*) (*)
2.7 5.1 2.0 (*) (*) (*) (*) (*)