6-12
Water pressure
switch WPS will
not operate
Water pressure is low
Water
temperature is
excessively high
Water flow rate is low
The remote
monitoring RM
is not output.
Disconnection of
Fu9
Short-circuit of RM
circuit
YES
YES
Is the fuse Fu9 circuit
disconnected?
Replace the Fu9
Check the wiring on ship
Correct it
NO
NO
NO
YES
Check the wiring
Correct
Check the controllerReplace
Is there any short circuit or
disconnection on the secondary side of
RM junction port (on ship)?
Is there any short circuit or
disconnection on the primary side of
RM connection port (on unit)?
Check for short circuit or disconnection at round crimp type
terminal board: from No.23, 24, 25, 26 to RM connection
port or connector type terminal board: from CN26 to RM
connection port
Faulty controller
Short-circ of RM
circuit on ship
Symptom Cause Checkpoint Remedy
The air cooling
evaporator fan
continues
rotating
Temperature in the
control box is high
Water pressure
switch WPS is
short-circuited
YES
YES
Is the condenser
fan stopped when the
CBS is cooled?
WPS has continuity
Check the water pressure,
water temperature, and
water volume
CBS OK
NO
NO
NO
YES
Faulty WPS
Faulty CBS
*CBS: Control box temperature sensor
The high pressure is
excessively high
The condenser fan continues rotating
Ⅶ Abnormal frosting on compressor
Ⅸ Others