is not output.
YES
YES
Is the fuse Fu9 circuit
disconnected?
Replace the Fu9
Check the wiring on ship
⇒Correct it
NO
NO
NO
YES
Check the wiring
⇒Correct
Check the controller⇒Replace
Is there any short circuit or
disconnection on the secondary side of
RM junction port (on ship)?
Is there any short circuit or
disconnection on the primary side of
RM connection port (on unit)?
Check for short circuit or disconnection at round crimp type
terminal board: from No.23, 24, 25, 26 to RM connection
port or connector type terminal board: from CN26 to RM
connection port
YES
YES
Is the condenser
fan stopped when the
CBS is cooled?
WPS has continuity
Check the water pressure,
water temperature, and
water volume
CBS OK
NO
NO
NO
YES
Faulty WPS
Faulty CBS
*CBS: Control box temperature sensor
The high pressure is
excessively high
The condenser fan continues rotating