7-7
7.11 Fuse protection table
Protection of:
Fuse 1 (250V, 10A) • High pressure switch (HPS)
• Compressor contactor (CC)
• Evaporator fan contactor high speed (EFH)
• Evaporator fan contactor low speed (EFL)
• Condensor fan contactor (CFC)
• Compressor terminal protector (CTP)
• Phase correction contactor (PCC1, PCC2)
Fuse 2 (250V, 10A) • Gas bypass solenoid valve (BSV)
• Defrost solenoid valve (DSV)
• Reheater solenoid valve (RSV) for dehumidification
Fuse 3 (250V, 10A) • Hot gas solenoid valve (HSV)
• Liquid solenoid valve (LSV)
• Injection solenoid valve (ISV)
• Economizer solenoid valve (ESV)
Fuse 4 (250V, 10A) • Modem
Fuse 6 (250V, 10A) • Recorder
Fuse 9 (250V, 10A) • Remote monitoring receptacle (RM)
Fuse 7 (250V, 10A) • CPU board
• Electronic expansion valve (EV)
• Suction modulating valve (SMV)
• LED display
• LCD screen
Fuse 8 (250V, 10A) • Spare
07LXE10E100以降(1-8白)E.qx08.9.33:03PMページ7-7