6-25
Prepare the emergency magnet.
Remove the suction proportional coil. (Removed together with the coil's lower rubber cover)
Bring the emergency magnet into contact with the coil mount section of the suction modulation valve
with indication "UP SIDE" located upward. (The emergency magnet is magnetically attracted to the
coil mount section by the driving magnet located inside.)
Turn the emergency magnet in the OPEN direction (clockwise) in the same place.
Ensure that the valve is fully open. (There is a small click sound.)
Yellow label
×Silver label
Coil mount section
Coil
Rubber cover
Emergency
magnet
(Part No.1896110)
UP SIDE
DOWN SIDE
OPEN
UP SIDE
DOWN SIDE
OPEN
Attention
The silver label is not used. (The silver
labels are used for LXE10E-A, 10E-1
and 10D.)
06LXE10E100(1-26)E.qx08.8.1310:35AMページ6-25