3-4
qPress the MANUAL DEFROST key.
wSelect "ON" indicated on the LED display using the key or the
key, and press the key to determine the setting, then the
defrost operation starts.
※The defrosting operation is not started when the temperature of
the evaporator outlet tube (EOS) is 20˚C or higher and that of the
evaporator inlet tube (EIS) is 5˚C or more.
※If the dehumidification function is available (the reheater coil is
turned ON), the defrosting operation may be started even when
the evaporator temperature is 5˚C or more.
MANUAL
DEFROST
MANUAL
DEFROST
q Indicate the temperature data required to be converted into "˚F"
on the LED or the LCD.
w Press the key, then the temperature data displayed in "˚C"
is converted into "˚F" for one minute.
※ If any other key is pressed during the "˚F" indication, the display
switches to "˚C".
LED
LCD
「℃」display 「°F」display