Test Operation Si-95
54 Test Operation Inverter K Series
1.5.2 Demand / low noise control
Connecting control input to the adaptor for outside control of outdoor units
enables demand and low noise control.
Demand control (figures indicate demand rate)
When short circuit between (1) and (C): Approx. 70% as a guideline
When short circuit between (2) and (C): Approx. 40% as a guideline
When short circuit between (3) and (C): Forced fan operation
Low noise control (Outdoor unit)
Running noise can be reduced by 2~ 3dB by controlling capacity of outdoor unit.
<System general>
When each system is set to the same address, the same demand control operation
is conducted.
<Common>
<Address setting (DS1 / DS2)>
Decide the address for each control unit from 0
~9 and set.
NOTES
Setting is within 8 groups when using a cool/heat central remote controller. Set from No. 0~No. 7.
Be sure to make the address No. of the PC board adaptor described above match the address No. of
function unit or outdoor unit (BS unit if using cool/heat simultaneous selection type).
(For detailed settings, see the installation instruction.)