The buzzer in the monitoring unit
This function is used if the buzzer in the monitoring unit will be
enabled in an alarm situation. Select the "Buzzer" setting.
There are three options for this setting:
Enabled. When the buzzer will be enabled for alarms.
Disabled. When the buzzer will not be enabled for alarms. This
setting is necessary during setup.
Timed. Where the buzzer will not sound alarms within the next
number of hours. The time is also set with this function.
When the time has run out, the setting will automati-
cally change to "Enabled".
This is where you select how long the buzzer must be enabled for
if there is an alarm.
With the setting = 0, the buzzer will be continuously enabled at
alarms. The buzzer is not disabled until the alarm button on the
front panel is enabled and "set alarm" is acknowledged. (2)
With a setting greater than 0, the buzzer will be active for the set
amount of time.
Remote alarm destinations via SMS
This function is used if an SMS is to be sent to a destination when
an alarm occurs. Select the setting "SMS 1".
There are three options for this setting:
Enabled. When the destination can expect to receive alarms.
Disabled. When the destination will not receive any alarms. This
setting is necessary during setup.
Timed. Where the destination will not receive alarms within
the next number of hours. The time is also set with this
function.
When the time has run out, the setting will automati-
cally change to "Enabled".
This is where you set the phone number of the SMS destination.
If there are more SMS message destinations (SMS 2 and SMS 3), they
must be set up in the same way.