0-02 Motor Speed Unit
Option: Function:
This parameter cannot be adjusted while the motor is running.
The display showing depends on settings in parameter 0-02 and
0-03. The default setting of parameters 0-02 and 0-03 depends
on which region of the world the frequency converter is supplied
to, but can be re-programmed as required.
NB!
Changing the
Motor Speed Unit
will reset certain
parameters to their initial value. It is recommen-
ded to select the motor speed unit first, before
modifying other parameters.
[0]
*
RPM Selects display of motor speed variables and parameters (i.e.
references, feedbacks and limits) in terms of motor speed
(RPM).
[1] Hz Selects display of motor speed variables and parameters (i.e.
references, feedbacks and limits) in terms of output frequency
to the motor (Hz).
0-03 Regional Settings
Option: Function:
[0]
*
International Sets par.1-20
Motor Power
units to kW and the default value
of par. 1-23
Motor Frequency
to 50 Hz.
[1] US Sets par.1-21
Motor Power
units to HP and the default value of
par. 1-23
Motor Frequency
to 60 Hz.
This parameter cannot be adjusted while the motor is running.
0-04 Operating State at Power-up (Hand)
Option: Function:
Select theoperating mode upon reconnection of the frequency
converter to mains voltage after power down in Hand (local)
operation mode.
[0] Resume Restarts the frequency converter maintaining the samelocal ref-
erence and the same start/stop settings (applied by [START/
STOP]) as before the frequency converter was powered down.
[1]
*
Forced stop, ref=old Restarts the frequency converter with a saved local reference,
after mains voltage reappears and after pressing [START].