4-32 Motor Feedback Loss Timeout
Range: Function:
0.05 s
*
[0.00 - 60.00 sec] Set the timeout value allowing the speed error set in par. 4-31
to be exceeded.
2.7.4. 4-5* Adjustable Warnings
Define adjustable warning limits for current, speed, reference and feedback. Warnings are shown
on the display, programmed output or serial bus.
Warnings are shown on display, programmed output or serial bus.
4-50 Warning Current Low
Range: Function:
0.00 A
*
[0.00 - par. 4-51] Enter the I
LOW
value. When the motor current falls below this
limit, the display reads
Current Low
. The signal outputs can be
programmed to produce a status signal on terminal 27 or 29 and
on relay output 01 or 02. Refer to the drawing in this section.