FC 300 CANopen
- P a r a m e t e r s -
48 MG.33.J1.02 VER. 050301 – VLT is a registered Danfoss trademark
10-01 Baud rate select
Option:
10 kbps [16]
20 kbps [17]
50 kbps [18]
100 kbps [19]
*125 kbps [20]
250 kbps [21]
500 kbps [22]
500 kbps [23]
1000 kbps [ 24]
Function:
Selection of the CANopen transmission speed. The
selection must correspond to the transmission
speed of the master and the other CANopen
nodes.
10-02 Drive Node ID
Range:
Bus Address 0 - 127 * 127
Function:
Selection of station address. Every station
connected to the same CANopen network must
have an unambiguous address.
10-05 Readout Transmit Error
Counter
Range:
0 - 255 * 0
Function:
Displays the Transmit Error Counter of the CAN
controller since the last power-up.
10-06 Readout Receive Error
Counter
Range:
0 - 255 * 0
Function:
Displays the Receive Error Counter of the CAN
controller since the last power-up.
10-07 Readout Bus Off Counter
Range:
0 255 * 0
Function:
Displays the number of Bus Off events since the
last power-up.
10-31 Store Data Values
Option:
*Off [0]
Store edit set-up [1]
Store all set-ups [2]
Function:
Par. 10-31 is used to activate storing of data in
non-volatile memory.
10-32 CANopen Revision
Range:
0 – 65535 N/A * 0 N/A
Function:
Par. 10-32 is used for EDS file creation.
10-33 Store Always
Option:
*Off [0]
On [1]
Function:
This parameter is used to select whether
parameter data received via the CANopen option
should be stored in EEPROM as default.
10-50 CANopen Process Data Config.
Write
Option:
*0 None [0]
16-80 Fieldbus CTW 1 [1]
16-82 Fieldbus REF 1 [2]
3-02 Minimum reference [3]
3-03 Maximum reference [4]
3-12 Catch up/slow down value [5]
3-41 Ramp 1 ramp up time [6]
3-42 Ramp 1 ramp down time [7]
3-51 Ramp 2 ramp up time [8]
3-52 Ramp 2 ramp down time [9]
3-80 Jog ramp time [10]
3-81 Quick stop ramp time [11]
4-11 Motor speed low limit (RPM) [12]
4-13 Motor speed high limit (RPM) [13]
4-16 Torque limit motor mode [14]
4-17 Torque limit generator mode [15]
8-90 Bus Jog 1 Speed [16]
8-91 Bus Jog 2 Speed [17]
Function:
Only elements [2] and [3] of this array can be
selected ([0] and [1] are fixed).
10-51 CANopen Process Data Config.
Read

Table of Contents

Other manuals for Danfoss FC 300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss FC 300 and is the answer not in the manual?

Danfoss FC 300 Specifications

General IconGeneral
EnclosureIP20
ApprovalscUL, UL, CE
EMC filterBuilt-in
Communication OptionsCANopen, PROFIBUS DP
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit
Output Voltage0-100% of supply voltage