Figure 4-52 IGV Harness Removal
4. Isolatethecompressorandrecovertherefrigerantaccordingtoindustrystandards.RefertoSection3.1
RefrigerantContainmentonpage41.
5. Removethe12M10x40fastenersthatsecuretheIGVHousingAssemblytothecompressorhousingand
pullthehousingawayfromthecompressor.RefertoFigure4-53IGVHousingRemoval.
Figure 4-53 IGV Housing Removal
Page 86 of 294 - M-SV-001-EN Rev. H 1/23/2023