The warning functions in parameters 221-228 are not
active during ramp-up after a start command, ramp-
down after a stop command or while stopped. The
warning functions are activated when the output fre-
quency has reached the selected reference. The sig-
nal outputs can be programmed to generate a warning
signal via terminal 42 or 45 and via the relay outputs.
In Closed loop, the unit for the feedback is program-
med in parameter 415 Process units.
Description of choice:
Set the required value within the feedback range (pa-
rameter 413 Minimum feedback, FB
MIN
, and 414
Maximum feedback, FB
MAX
).
228
Warning: High feedback, FB
HIGH
(WARN. HIGH FDBK)
Value:
FB
LOW
(parameter 227) - 999,999.999 999.999,999
Function:
If the feedback signal is above the limit, FB
HIGH
, pro-
grammed in this parameter, the display will show a
flashing FEEDBACK HIGH.
The warning functions in parameters 221-228 are not
active during ramp-up after a start command, ramp-
down after a stop command or while stopped. The
warning functions are activated when the output fre-
quency has reached the selected reference.
The signal outputs can be programmed to generate a
warning signal via terminal 42 or 45 and via the relay
outputs.
In Closed loop, the unit for the feedback is program-
med in parameter 415 Process units.
Description of choice:
Set the required value within the feedback range (pa-
rameter 413 Minimum feedback, FB
MIN
, and 414 Max-
imum feedback, FB
MAX
).
VLT
®
6000 HVAC Series
MG.61.B5.02 - VLT
®
is a registered Danfoss trademark 123
Programming