Mains supply (L1, L2, L3)
Mains supply (L1, L2, L3):
Supply voltage 200-240 V units 3 x 200/208/220/230/240 V ±10%
Supply voltage 380-460 V units 3 x 380/400/415/440/460 V ±10%
Supply voltage 525-600 V units 3 x 525/550/575/600 V ±10%
Supply frequency 48-62 Hz ± 1%
Max. imbalance of supply voltage:
VLT 6002-6011, 380-460 V and 525-600 V and VLT 6002-6005, 200-240 V ±2.0% of rated supply voltage
VLT 6016-6072, 380-460 V and 525-600 V and VLT 6006-6032, 200-240 V ±1.5% of rated supply voltage
VLT 6102-6602, 380-460 V and VLT 6042-6062, 200-240 V ±3.0% of rated supply voltage
VLT 6102-6652, 525-600 V ±3% of rated supply voltage
True Power factor (λ)
0.90 nominal at rated load
Displacement Power Factor (cos. )
near unity (>0.98)
No. of switches on supply input L1, L2, L3 approx. 1 time/2 min.
Max. short-circuit current 100.000 A
VLT output data (U, V, W):
Output voltage 0-100% of supply voltage
Output frequency:
Output frequency 6002-6032, 200-240V
0-120 Hz, 0-1000 Hz
Output frequency 6042-6062, 200-240V 0-120 Hz, 0-450 Hz
Output frequency 6002-6062, 380-460V 0-120 Hz, 0-1000 Hz
Output frequency 6072-6602, 380-460V 0-120 Hz, 0-450 Hz
Output frequency 6002-6016, 525-600V 0-120 Hz, 0-1000 Hz
Output frequency 6022-6062, 525-600V 0-120 Hz, 0-450 Hz
Output frequency 6072, 525-600V 0-120 Hz, 0-450 Hz
Output frequency 6102-6352, 525-600V 0-132 Hz, 0-200 Hz
Output frequency 6402-6652, 525-600V 0-132 Hz, 0-150 Hz
Rated motor voltage, 200-240 V units 200/208/220/230/240 V
Rated motor voltage, 380-460 V units 380/400/415/440/460 V
Rated motor voltage, 525-600 V units 525/550/575 V
Rated motor frequency 50/60 Hz
Switching on output Unlimited
Ramp times 1 - 3600 sec.
Torque characteristics:
Starting torque 110% for 1 min.
Starting torque (parameter 110 High break-away torque) Max. torque: 160% for 0.5 sec.
Acceleration torque 100%
Overload torque 110%
VLT
®
6000 HVAC Series
MG.61.B5.02 - VLT
®
is a registered Danfoss trademark 43
Installation