Mains supply (L1, L2, L3)
Mains supply (L1, L2, L3):
Supply voltage 200-240 V units 3 x 200/208/220/230/240 V ±10%
Supply voltage 380-460 V units 3 x 380/400/415/440/460 V ±10%
Supply voltage 525-600 V units 3 x 525/550/575/600 V ±10%
Supply frequency 48-62 Hz ± 1%
Max. imbalance of supply voltage:
VLT 6002-6011, 380-460 V and 525-600 V and VLT 6002-6005, 200-240 V ±2.0% of rated supply voltage
VLT 6016-6072, 380-460 V and 525-600 V and VLT 6006-6032, 200-240 V ±1.5% of rated supply voltage
VLT 6102-6602, 380-460 V and VLT 6042-6062, 200-240 V ±3.0% of rated supply voltage
VLT 6102-6652, 525-600 V ±3% of rated supply voltage
True Power factor (λ)
0.90 nominal at rated load
Displacement Power Factor (cos. )
near unity (>0.98)
No. of switches on supply input L1, L2, L3 approx. 1 time/2 min.
Max. short-circuit current 100.000 A
VLT output data (U, V, W):
Output voltage 0-100% of supply voltage
Output frequency:
Output frequency 6002-6032, 200-240V
0-120 Hz, 0-1000 Hz
Output frequency 6042-6062, 200-240V 0-120 Hz, 0-450 Hz
Output frequency 6002-6062, 380-460V 0-120 Hz, 0-1000 Hz
Output frequency 6072-6602, 380-460V 0-120 Hz, 0-450 Hz
Output frequency 6002-6016, 525-600V 0-120 Hz, 0-1000 Hz
Output frequency 6022-6062, 525-600V 0-120 Hz, 0-450 Hz
Output frequency 6072, 525-600V 0-120 Hz, 0-450 Hz
Output frequency 6102-6352, 525-600V 0-132 Hz, 0-200 Hz
Output frequency 6402-6652, 525-600V 0-132 Hz, 0-150 Hz
Rated motor voltage, 200-240 V units 200/208/220/230/240 V
Rated motor voltage, 380-460 V units 380/400/415/440/460 V
Rated motor voltage, 525-600 V units 525/550/575 V
Rated motor frequency 50/60 Hz
Switching on output Unlimited
Ramp times 1 - 3600 sec.
Torque characteristics:
Starting torque 110% for 1 min.
Starting torque (parameter 110 High break-away torque) Max. torque: 160% for 0.5 sec.
Acceleration torque 100%
Overload torque 110%
VLT
®
6000 HVAC Series
MG.61.B5.02 - VLT
®
is a registered Danfoss trademark 43
Installation

Table of Contents

Other manuals for Danfoss VLT 6000 HVAC Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 6000 HVAC Series and is the answer not in the manual?

Danfoss VLT 6000 HVAC Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 6000 HVAC Series
CategoryDC Drives
LanguageEnglish

Related product manuals