Technical data, mains supply 3 x 525-600 V
According to international requirements VLT type 6002 6003 6004 6005 6006 6008 6011
Output current I
VLT,N
[A] (550 V) 2.6 2.9 4.1 5.2 6.4 9.5 11.5
I
VLT, MAX
(60 s) [A] (550V)
2.9
3.2 4.5 5.7 7.0 10.5 12.7
I
VLT,N
[A] (575 V)
2.4
2.7 3.9 4.9 6.1 9.0 11.0
I
VLT, MAX
(60 s) [A] (575 V) 2.6 3.0 4.3 5.4 6.7 9.9 12.1
Output S
VLT,N
[kVA] (550 V)
2.5 2.8 3.9 5.0 6.1 9.0 11.0
S
VLT,N
[kVA] (575 V)
2.4 2.7 3.9 4.9 6.1 9.0 11.0
Typical shaft output P
VLT,N
[kW]
1.1 1.5 2.2 3 4 5.5 7.5
Typical shaft output P
VLT,N
[HP]
1.5 2 3 4 5 7.5 10
Max. copper cable cross-section to motor and load-
sharing
[mm
2
]
4
4 4 4 4 4 4
[AWG]
2)
10 10 10 10 10 10 10
Rated Input
Current
I
VLT,N
[A] (550 V)
I
VLT,N
[A] (600 V)
2.5
2.2
2.8
2.5
4.0
3.6
5.1
4.6
6.2
5.7
9.2
8.4
11.2
10.3
Max.copper cable cross-section, power
[mm
2
]
4
4 4 4 4 4 4
[AWG]
2)
10 10 10 10 10 10 10
Max. prefuses (mains)
1)
[ - ]/UL [A]
3
4 5 6 8 10 15
Efficiency 0.96
Weight IP20 /
NEMA 1
[kg]
[Ibs]
10.5
23
10.5
23
10.5
23
10.5
23
10.5
23
10.5
23
10.5
23
Estimated power loss at max. load (550 V) [W] 65 73 103 131 161 238 288
Estimated power loss at max. load (600V) [W]
63 71 102 129 160 236 288
Enclosure IP 20/NEMA 1
1.
For type of fuse, see section Fuses.
2. American Wire Gauge (AWG).
3. Min. cable cross-section is the smallest cable cross-section allowed to be fitted into the terminals to comply with IP20. Always
comply with national and local regulations on min. cable cross-section.
VLT
®
6000 HVAC Series
54 MG.61.B5.02 - VLT
®
is a registered Danfoss trademark

Table of Contents

Other manuals for Danfoss VLT 6000 HVAC Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 6000 HVAC Series and is the answer not in the manual?

Danfoss VLT 6000 HVAC Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 6000 HVAC Series
CategoryDC Drives
LanguageEnglish

Related product manuals