Technical data, mains supply 3 x 525-600 V
According to international requirements 6016 6022 6027
603
2
6042 6052 6062 6072
Output current I
VLT,N
[A] (550 V)
18 23 28 34 43 54 65 81
I
VLT, MAX
(60 s) [A] (550V)
20 25 31 37 47 59 72 89
I
VLT,N
[A] (575 V) 17 22 27 32 41 52 62 77
I
VLT, MAX
(60 s) [A] (575 V) 19 24 30 35 45 57 68 85
Output
S
VLT,N
[kVA] (550 V)
17 22 27 32 41 51 62 77
S
VLT,N
[kVA] (575 V) 17 22 27 32 41 52 62 77
Typical shaft output P
VLT,N
[kW] 11 15 18.5 22 30 37 45 55
Typical shaft output P
VLT,N
[HP]
15
20 25 30 40 50 60 75
Max. copper cable
cross-section to motor
and loadsharing
4)
[mm
2
]
16 16 16 35 35 50 50 50
[AWG]
2)
6 6 6 2 2 1/0 1/0 1/0
Min. cable cross-section
to motor and loadshar-
ing
3)
[mm
2
]
0.5
0.5 0.5 10 10 16 16 16
[AWG]
2)
20 20 20 8 8 6 6 6
Rated Input Current
I
VLT.N
[A] (550 V) 18 22 27 33 42 53 63 79
I
VLT.N
[A] (600 V)
16
21 25 30 38 49 38 72
Max copper cable cross
section, power
4)
[mm2]
16 16 16 35 35 50 50 50
[AWG]
2)
6 6 6 2 2 1/0 1/0 1/0
Max. prefuses (mains)
1)
[-]/UL [A]
20
30 35 45 60 75 90 100
Efficiency 0.96
Weight IP20 / NEMA 1
[kg]
[Ibs]
23
51
23
51
23
51
30
66
30
66
48
106
48
106
48
106
Estimated power loss at max. load (550 V) [W] 451 576 702 852 1077 1353 1628 2029
Estimated power loss at max. load (600 V) [W]
446 576 707 838 1074 1362 1624 2016
Enclosure
NEMA 1
1.
For type of fuse, see section Fuses.
2. American Wire Gauge (AWG).
3. Min. cable cross-section is the smallest cable cross-section allowed to be fitted into the terminals to comply with IP20.
Always comply with national and local regulations on min. cable cross-section.
4.
Aluminium cables with cross-section above 35 mm
2
must be connected by use of an Al-Cu connector.
VLT
®
6000 HVAC Series
MG.61.B5.02 - VLT
®
is a registered Danfoss trademark 55
Installation