Technical data, mains supply 3 x 380-460V
According to international requirements VLT type 6002 6003 6004 6005 6006 6008 6011
Output current
I
VLT,N
[A] (380-440
V)
3.0 4.1 5.6 7.2 10.0 13.0 16.0
I
VLT, MAX
(60 s) [A]
(380-440 V)
3.3 4.5 6.2 7.9 11.0 14.3 17.6
I
VLT, N
[A] (441-460
V)
3.0 3.4 4.8 6.3 8.2 11.0 14.0
I
VLT, MAX
(60 s) [A]
(441-460 V)
3.3 3.7 5.3 6.9 9.0 12.1 15.4
Output power
S
VLT,N
[kVA] (400 V)
2.2 2.9 4.0 5.2 7.2 9.3 11.5
S
VLT,N
[kVA] (460 V) 2.4 2.7 3.8 5.0 6.5 8.8 11.2
Typical shaft out-
put
P
VLT,N
[kW]
1.1 1.5 2.2 3.0 4.0 5.5 7.5
Typical shaft out-
put
P
VLT,N
[HP] 1.5 2 3 - 5 7.5 10
Max. cable cross-
section to motor
[mm
2
]/[AWG]
2) 4)
4/10 4/10 4/10 4/10 4/10 4/10 4/10
Max. input current
I
L,N
[A] (380 V) 2.8 3.8 5.3 7.0 9.1 12.2 15.0
(RMS) I
L,N
[A] (460 V)
2.5 3.4 4.8 6.0 8.3 10.6 14.0
Max. cable
cross-section pow-
er
[mm
2
]/[AWG]
2) 4)
4/10 4/10 4/10 4/10 4/10 4/10 4/10
Max. pre-fuses
[-]/UL
1)
[A]
16/6 16/10 16/10 16/15 25/20 25/25 35/30
Efficiency
3)
0.96
0.96 0.96 0.96 0.96 0.96 0.96
Weight IP 20 [kg] 8 8 8.5 8.5 10.5 10.5 10.5
Weight IP 54 [kg] 11.5 11.5 12 12 14 14 14
Power loss at
max. load. [W]
Total 67 92 110 139 198 250 295
Enclosure VLT type IP 20/IP 54
1.
For type of fuse, see section Fuses.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Max. cable cross section is the maximum possible cable cross section that can be fitted on the terminals.
Always comply with national and local regulations on min. cable cross-section.
VLT
®
6000 HVAC Series
MG.61.B5.02 - VLT
®
is a registered Danfoss trademark 49
Installation