Function:
The Fire Mode frequency is the fixed output frequency
used when Fire Mode is activated via terminal 16 or
17.
Description of choice:
Set the required output frequency to be used during
Fire Mode.
432 Fire mode bypass delay, s
(FIRE M. BYP. DELAY)
Value:
0 - 600 sec.
0 sec.
Function:
This time delay is used in case the frequency converter
trips caused by an alarm. After a trip, and the delay
time has passed, an output is set. Please see descrip-
tion of Fire Mode and parameter 319, 321, 323 and
326 for further information.
Description of choice:
Set the required time delay before trip and setting the
output.
483 Dynamic DC link compensation
(DC link comp.)
Value:
Off [0]
On [1]
Function:
The frequency converter includes a feature, which en-
sures that the output voltage is independent of any
voltage fluctuation in the DC link, e.g. caused by fast
fluctuation in the mains supply voltage. The benefit is
a very steady torque on motor shaft (low torque ripple)
under most mains conditions.
Description of choice:
In some cases this dynamic compensation can cause
resonance’s in the DC link and should then be disa-
bled. Typical cases are where a line choke or a passive
harmonic filter (e.g. filters AHF005/010) is mounted in
the mains supply to the frequency converter to sup-
press harmonics. Can also occur on mains with low
short circuit ratio.
VLT
®
6000 HVAC Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
154 MG.61.B5.02 - VLT
®
is a registered Danfoss trademark

Table of Contents

Other manuals for Danfoss VLT 6000 HVAC Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 6000 HVAC Series and is the answer not in the manual?

Danfoss VLT 6000 HVAC Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 6000 HVAC Series
CategoryDC Drives
LanguageEnglish

Related product manuals