Example - Write a parameter value:
Parameter 202 Output frequency high limit, f
MAX
is to
be changed to 100 Hz. This value must be remember
after a power failure, so it is written in EEPROM.
PKE = E0CA Hex - Write to parameter 202
Output frequency high limit, f
MAX
IND = 0000 Hex
PWE
HIGH
= 0000 Hex
PWE
LOW
= 03E8 Hex - Data value 1000, corre-
sponding to 100 Hz, see Conversion.
The reply from the slave to the master will be:
Example - Choice of a data value:
kW [20] is to be selected in parameter 415 Process
units. This value must be remembered after a power
failure, so it is written in EEPROM.
PKE = E19F Hex - Write to parameter 415
Process units
IND = 0000 Hex
PWE
HIGH
= 0000 Hex
PWE
LOW
= 0014 Hex - Choose data choice kW
[20]
The reply from the slave to the master will be:
Example - Read a parameter value:
The value in parameter 206 Ramp-up time is required.
The master sends the following enquiry:
PKE = 10CE Hex - read parameter 206
Ramp-up time
IND = 0000 Hex
PWE
HIGH
= 0000 Hex
PWE
LOW
= 0000 Hex
If the parameter value in parameter 206 Ramp-up
time is 10 seconds, the reply from the slave to the
master will be as follows:
VLT
®
6000 HVAC Series
160 MG.61.B5.02 - VLT
®
is a registered Danfoss trademark

Table of Contents

Other manuals for Danfoss VLT 6000 HVAC Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 6000 HVAC Series and is the answer not in the manual?

Danfoss VLT 6000 HVAC Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 6000 HVAC Series
CategoryDC Drives
LanguageEnglish

Related product manuals