ALARM: 32
Motor phase W missing
(MISSING MOT.PHASE U):
Motor phase W between frequency converter and mo-
tor is missing.
Turn off the frequency converter and check motor
phase W.
WARNING/ALARM: 34
HPFB communication fault
(HPFB COMM. FAULT)
The serial communication on the communication op-
tion card is not working.
ALARM: 37
Inverter fault (GATE DRIVE FAULT):
IGBT or the power card is defective. Contact your
Danfoss supplier.
Auto-optimisation warnings 39-42
Automatic motor adaptation has stopped, since some
parameters have probably been set wrongly, or the
motor used in too big/small for AMA to be carried out.
A choice must thus be made by pressing [CHANGE
DATA] and choosing ‘Continue’ + [OK] or ‘Stop’ + [OK].
If parameters need to be changed, select ‘Stop’; start
up AMA all over.
WARNING: 39
CHECK PAR. 104, 106
Parameters 104 Motor frequency f
M,N
, or 106 Rated
motor speed n
M,N
, have probably not been set cor-
rectly. Check the setting and select ‘Continue’ or
[STOP].
WARNING: 40
CHECK PAR. 103, 105
Parameter 103 Motor voltage, U
M,N
or 105 Motor cur-
rent, I
M,N
has not been set correctly. Correct the setting
and restart AMA.
WARNING: 41
MOTOR TOO BIG (MOTOR TOO BIG)
The motor used is probably too big for AMA to be car-
ried out. The setting in parameter 102 Motor power,
P
M,N
may not match the motor. Check the motor and
choose ‘Continue’ or [STOP].
WARNING: 42
MOTOR TOO SMALL (MOTOR TOO SMALL)
The motor used is probably too small for AMA to be
carried out. The setting in parameter 102 Motor power,
P
M,N
may not match the motor. Check the motor and
select ‘Continue’ or [STOP].
ALARM: 60
Safety stop (EXTERNAL FAULT)
Terminal 27 (parameter 304 Digital inputs) has been
programmed for a Safety interlock [3] and is a logic ‘0’.
WARNING: 61
Output frequency low (FOUT < FLOW)
The output frequency is lower than parameter 223
Warning: Low frequency, f
LOW
.
WARNING: 62
Output frequency high (FOUT > FHIGH)
The output frequency is higher than parameter 224
Warning: High frequency, f
HIGH
.
WARNING/ALARM: 63
Output current low (I MOTOR < I LOW)
The output current is lower than parameter 221 Warn-
ing: Low current, I
LOW
. Select the required function in
parameter 409 Function in case of no load.
WARNING: 64
Output current high (I MOTOR > I HIGH)
The output current is higher than parameter 222 Warn-
ing: High current, I
HIGH
.
WARNING: 65
Feedback low (FEEDBACK < FDB LOW)
The resulting feedback value is lower than parameter
227 Warning: Low feedback, FB
LOW
.
WARNING: 66
Feedback high (FEEDBACK > FDB HIGH)
The resulting feedback value is higher than parameter
228 Warning: High feedback, FB
HIGH
.
WARNING: 67
Remote reference low (REF. < REF LOW)
The remote reference is lower than parameter 225
Warning: Low reference, RE
FLOW
.
WARNING: 68
Remote reference high (REF. > REF HIGH)
The remote reference is higher than parameter 226
Warning: High reference, REF
HIGH
.
WARNING: 69
Temperature auto derate (TEMP.AUTO DERATE)
The heat sink temperature has exceeded the maxi-
mum value and the auto derating function (par. 411) is
active. Warning: Temp. Auto derate.
VLT
®
6000 HVAC Series
192 MG.61.B5.02 - VLT
®
is a registered Danfoss trademark

Table of Contents

Other manuals for Danfoss VLT 6000 HVAC Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT 6000 HVAC Series and is the answer not in the manual?

Danfoss VLT 6000 HVAC Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT 6000 HVAC Series
CategoryDC Drives
LanguageEnglish

Related product manuals