Immunity, continued
Burst Surge
ESD
Radiated electro- Mains RF common Radiated radio
Basic standard IEC 1000-4-4 IEC 1000-4-5 1000-4-2 magnetic field distortion mode voltage freq.elect.field
IEC 1000-4-3 VDE 0160 ENV 50141 ENV 50140
Acceptance criterion B B B A A A
Port connection CM DM CM - - CM CM
Line OK OK - - - OK OK -
Motor OK - - - - - OK -
Control lines OK - OK - - - OK -
PROFIBUS option OK - OK - - - OK -
Signal Interface<3 m OK - - - - - - -
Enclosure - - - OK OK - - OK
Load sharing OK - - - - - OK -
Standard bus OK - OK - - - OK -
Basic specifications
- - - -
Line 4 kV/5kHz/DCN 2 kV/2Ω 4 kV/12Ω - -
2,3 x U
N
2)
10 V
RMS
-
Motor 4 kV/5kHz/CCC - - - - - 10 V
RMS
-
Control lines 2 kV/5kHz/CCC -
2 kV/2Ω
1)
- - - 10 V
RMS
-
PROFIBUS option 2 kV/5kHz/CCC -
2 kV/2Ω
1)
- - - 10 V
RMS
-
Signal interface<3 m 1 kV/5kHz/CCC - - - - - 10 V
RMS
-
Enclosure - - - 8 kV AD
6 kV CD
10 V/m
- - -
Load sharing 4 kV/5kHz/CCC - - - - - 10 V
RMS
-
Standard bus 2 kV/5kHz/CCC -
4 kV/2
1)
- - - 10 V
RMS
-
DM: Differential mode
CM: Common mode
CCC: Capacitive clamp coupling
DCN: Direct coupling network
1
) Injection on cable shield
2
)
2.3 x U
N
: max. test pulse 380 V
AC
: Class 2/1250 V
PEAK
, 415 VAC: Class 1/1350 V
PEAK
VLT
®
6000 HVAC Series
MG.61.B5.02 - VLT
®
is a registered Danfoss trademark 207
All about VLT 6000
HVAC