Installation of VLT 6402-6602 380-460 V and VLT
6502-6652, 525-600 V Compact IP 21 and IP 54
Cooling Side-by-side
All units in the above-mentioned series require a mini-
mum space of 225 mm above the enclosure and must
be installed on a flat level surface. This applies to both
IP 21 and IP 54 units.
Gaining access requires a minimum space of 579 mm
in front of the frequency converter.
All IP 21 and IP 54 units in the above-mentioned series
can be installed side by side without any space between
them, since these units do not require cooling on the
sides.