Parameter Data
Enter or change parameter dataor settings in accord-
ance with the following procedure.
1. Press Quick Menu key.
2. Use ‘+’ and ‘-’ keys to find parameter you
choose to edit.
3. Press Change Data key.
4. Use ‘+’ and ‘-’ keys to select correct param-
eter setting. To move to a different digit within
parameter, use < and > arrows. Flashing cur-
sor indicates digit selected to change.
5. Press Cancel key to disregard change, or
press OK key to accept change and enter
new setting.
Example of Changing Parameter Data
Assume parameter 206, Ramp Up Time, is set at 60
seconds. Change the ramp up time to 100 seconds in
accordance with the following procedure.
1. Press Quick Menu key.
2. Press ‘+’ key until you reach Parameter 206,
Ramp Up Time.
3. Press Change Data key.
4. Press < key twice – hundreds digit will flash.
5. Press ‘+’ key once to change hundreds digit
to ‘1.’
6. Press > key to change to tens digit.
7. Press ‘-’ key until ‘6’ counts down to ‘0’ and
setting for Ramp Up Time reads ‘100 s.’
8. Press OK key to enter new value into drive
controller.
NB!
Programming of extended parameters
functions available through EXTENDED
MENU key is done in accordance with
same procedure as described for Quick
Menu functions.
VLT
®
6000 HVAC Series
MG.61.B5.02 - VLT
®
is a registered Danfoss trademark 99
Programming