Selection table, 440–480 V, 60 Hz
Frequency converter values Filter values
Power rating
441–500
V
Current rating Ordering numbers Power loss
Acoustic
noise
Enclosure sizes, enclosure protection ratings, and
fan concept
T4/T5 AHF 005 AHF 010 AHF 005 AHF 010 AHF 005 AHF 010 AHF 005 AHF 010
[kW]
1)
[hp]
2)
[A] [A] [A] IP00 IP20 IP00 IP20 [W] [W] [dB(A)] IP00 IP20 IP00 IP20
315 450 531 522 522
130B1900
+
130B2200
130B1765
+
130B1766
130B1783
+
130B1784
130B1497
+
130B1498
2576 1810 <80
See individual lters
355 500 580 582 582 2 x 130B2200 2 x 130B1766 2 x 130B1784 2 x 130B1498 2812 1904 <80
400 550 667 671 671
130B2200
+
130B3168
130B1766
+
130B3167
130B1784
+
130B3166
130B1498
+
130B3165
2798 2080 <80
450 600 771 710 710 2 x 130B2257 2 x 130B1768 2 x 130B1785 2 x 130B1499 3020 2350 <80
500 650 759 760 760 2 x 130B3168 2 x 130B3167 2 x 130B3166 2 x 130B3165 3362 2717 <80
560 750 867 872 872 2 x 130B2259 2 x 130B1769 2 x 130B1786 2 x 130B1751 3704 3084 <80
630 900 1022 1065 1065 3 x 130B2257 3 x 130B1768 3 x 130B1785 3 x 130B1499 4530 3525 <80
710 1000 1129 1140 1140 3 x 130B3168 3 x 130B3167 3 x 130B3166 3 x 130B3165 4872 3892 <80
800 1200 1344 1308 1308 3 x 130B2259 3 x 130B1769 3 x 130B1786 3 x 130B1751 5556 4626 <80
1000 1350 1490 1582 1582
2 x 130B2257
+
2 x 130B2259
2 x 130B1768
+
2 x 130B1769
2 x 130B1785
+
2 x 130B1786
2 x 130B1499
+
2 x 130B1751
6724 5434 <80
1) kW power ratings in selection table are the actual operating power and not necessarily the type code power rating. Changing operating conditions between HO and NO changes the actual operating
conditions and the lter selection must reect actual operating conditions.
2) Typical hp shaft output at 460 V.
3) Filters are used as paralleling for 500 kW and 710 kW frequency converters.
Table 5.5 440–480 V, 60 Hz