EasyManua.ls Logo

Danfoss VLT AHF 005

Danfoss VLT AHF 005
156 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Introduction to Harmonics and Mitigation
2.1 Harmonics and Mitigation
2.1.1 Linear Loads
On a sinusoidal AC supply, a purely resistive load (for
example an incandescent light bulb) draws a sinusoidal
current in phase with the supply voltage.
The power dissipated by the load is:
P = U × I
For reactive loads (such as an asynchronous motor), the
current is no longer in phase with the voltage. Instead, the
current lags the voltage creating a lagging power factor
with a value less than 1. In the case of capacitive loads, the
current is ahead of the voltage, creating a leading power
factor with a value less than 1.
Illustration 2.1 Current Creating a True Power Factor
In this case, the AC power has 3 components:
Real power, (P).
Reactive power, (Q).
Apparent power, (S).
The apparent power is:
S = U × I
(where S=[kVA], P=[kW] and Q=[kVAR]).
In the case of a perfectly sinusoidal waveform, P, Q, and S
can be expressed as vectors that form a triangle:
S
2
= P
2
+ Q
2
P
S
Q
φ
130BB538.10
Illustration 2.2 Sinusoidal Waveform
The displacement angle between current and voltage is φ.
The displacement power factor is the ratio between the
active power (P) and apparent power (S):
DPF =
P
S
= cos(ϕ)
2.1.2 Non-linear Loads
Non-linear loads (such as diode rectiers) draw a non-
sinusoidal current. Illustration 2.3 shows the current drawn
by a 6-pulse rectier on a 3-phase supply.
A non-sinusoidal waveform can be decomposed in a sum
of sinusoidal waveforms with periods equal to integer
multiples of the fundamental waveform.
f (t) =
a
h
× sin
hω
1
t
See Illustration 2.3.
Introduction to Harmonics a... Design Guide
MG80C502 Danfoss A/S © 10/2016 All rights reserved. 9
2 2

Table of Contents

Related product manuals