Selection table, 500–690 V, 50 Hz
Frequency converter values Filter values
Power
rating
Input current
Current
rating at
690 V
Ordering numbers Power loss
Acoustic
noise
Enclosure sizes, enclosure protection ratings, and
fan concept
T6/T7
T6 T7 T7
525–
550 V
525–
550 V
690 V
AHF
005
AHF
010
AHF 005
2)
AHF 010
3)
AHF
005
AHF
010
AHF 005 AHF 010
[kW]
1)
[A] [A] [A] [A] [A] IP00 IP20 IP00 IP20 [W] [W] [dB(A)] IP00 IP20 IP00 IP20
11 17.2 15.0 14.5 15 15 130B5000 130B5088 130B5297 130B5280 298 224 <70 X3 IP00 X3 IP20 if2 X3 IP00 X3 IP20 if2
15 20.9 19.5 19.5 20 20 130B5017 130B5089 130B5298 130B5281 335 233 <70 X3 IP00 X3 IP20 if2 X3 IP00 X3 IP20 if2
18.5 25.4 24 24 24 24 130B5018 130B5090 130B5299 130B5282 396 242 <70 X3 IP00 X3 IP20 ef2 X3 IP00 X3 IP20 ef2
22 32.7 29 29 29 29 130B5019 130B5092 130B5302 130B5283 482 274 <70 X4 IP00 X4 IP20 ef2 X4 IP00 X4 IP20 ef2
30 39.0 36 36 36 36 130B5021 130B5125 130B5404 130B5284 574 352 <70 X4 IP00 X4 IP20 ef2 X4 IP00 X4 IP20 ef2
37 49.0 49 48 50 50 130B5022 130B5144 130B5310 130B5285 688 374 <70 X5 IP00 X5 IP20 ef2 X5 IP00 X5 IP20 ef2
45 59.0 59 58 58 58 130B5023 130B5168 130B5324 130B5286 747 428 <70 X5 IP00 X5 IP20 ef2 X5 IP00 X5 IP20 ef2
55 78.9 77 77 77 77 130B5024 130B5169 130B5325 130B5287 841 488 <72 X6 IP00 X6 IP20 ef2 X6 IP00 X6 IP20 ef2
75 95.3 89 87 87 87 130B5025 130B5170 130B5326 130B5288 962 692 <72 X6 IP00 X6 IP20 ef2 X6 IP00 X6 IP20 ef2
90 124.3 110 109 109 109 130B5026 130B5172 130B5327 130B5289 1080 743 <72 X6 IP00 X6 IP20 ef2 X6 IP00 X6 IP20 ef2
110 – 130 128 128 128 130B5028 130B5195 130B5328 130B5290 1194 864 <72 X6 IP00 X6 IP20 ef2 X6 IP00 X6 IP20 ef2
132 – 158 155 155 155 130B5029 130B5196 130B5329 130B5291 1288 905 <72 X7 IP00 X7 IP20 ef2 X7 IP00 X7 IP20 ef2
160 – 198 197 197 197 130B5042 130B5197 130B5330 130B5292 1406 952 <72 X7 IP00 X7 IP20 ef2 X7 IP00 X7 IP20 ef2
200 – 245 240 240 240 130B5066 130B5198 130B5331 130B5293 1510 1175 <75 X8 IP00 X8 IP20 ef2 X7 IP00 X7 IP20 ef2
250 – 299 296 296 296 130B5076 130B5199 130B5332 130B5294 1852 1288 <75 X8 IP00 X8 IP20 ef2 X8 IP00 X8 IP20 ef2
315 – 355 352 394 366 2 x 130B5042 2 x 130B5197 130B5333 130B5295 2812 1542 <77
See individual lters
X8 IP00 X8 IP20 ef2
355 – 381 366 394 395 2 x 130B5042 2 x 130B5197 130B5334 130B5296 2812 1852 <77 X8 IP00 X8 IP20 ef2
400 – 413 400 437 437
130B5042 +
130B5066
130B5197 +
130B5198
130B5330 +
130B5331
130B5292 +
130B5293
2916 2127 <80
See individual lters
500 – 504 482 536 536
130B5066 +
130B5076
130B5198 +
130B5199
130B5331 +
130B5332
130B5293 +
130B5294
3362 2463 <80
560 – 574 549 592 592 2 x 130B5076 2 x 130B5199 2 x 130B5332 2 x 130B5294 3704 2576 <80
630 – 642 613 662 662
130B5076 +
2 x 130B5042
130B5199 +
2 x 130B5197
130B5332 +
130B5333
130B5294 +
130B5295
4664 2830 <80
710 – 743 711 788 732 4 x 130B5042 4 x 130B5197 2 x 130B5333 2 x 130B5295 5624 3084 <80
800 – 866 828 888 888 3 x 130B5076 3 x 130B5199 3 x 130B5332 3 x 130B5294 5556 3864 <80
900 – 962 920 986 958
2 x 130B5076
+
2 x 130B5042
2 x 130B5199
+
2 x 130B5197
2 x 130B5332
+
130B5333
2 x 130B5294 +
130B5295
6516 4118 <80
1) kW power ratings in selection table are the actual operating power and not necessarily the type code power rating. Changing operating conditions between HO and NO changes the
actual operating conditions and the lter selection must reect actual operating conditions.
2) Operating the AHF 005 at 525 V mains supply improves the harmonic performance level to a typical value of 3% THDi.
Operating the AHF 010 at 525 V mains supply improves the harmonic performance level to a typical value of 8%.
Table 5.7 500–690 V, 50 Hz
Selection of Advanced Harmo... Design Guide
MG80C502 Danfoss A/S © 10/2016 All rights reserved. 39
5 5