AHF version
AHF
enclosure
size
AHF terminal connections
600 V/60 Hz Terminals X1 and X2 Terminals X3 and X4 Terminasl A and B PE
AHF
005
AHF
010
Cable
cross-
sections
[mm
2
(AWG/
MCM)]
Termina-
tion
Torque
[Nm (in-
lb)]
Cable
cross-
sections
[mm
2
(AWG/
MCM)]
Termina-
tion
Torque
[Nm (in-
lb)]
Cable
cross-
sections
[mm
2
(AWG/
MCM)]
Termina-
tion
Torque
[Nm (in-
lb)]
Type
Torque
[Nm (in-
lb)]
[A] [A] Type
15
20
24
15
20
24
X3
1.5–25
(16–4)
Cable
end
sleeve
3.5 (31)
±10%
1.5–16
(16–6)
Cable
end
sleeve
2.4 (21.2)
±10%
0.5–4
(20–12)
Cable
end
sleeve
0.8 (7.1)
±10%
M8
10 (88.5)
±10%
29
36
29
36
X4
1.5–50
(16–
1-1/0)
Cable
end
sleeve
4 (35.4)
±10%
1.5–25
(16–4)
Cable
end
sleeve
3.5 (31)
±10%
0.5–4
(20–12)
Cable
end
sleeve
0.8 (7.1)
±10%
M8
10 (88.5)
±10%
50
58
50
58
X5
10–70
(8–2/0)
Cable
end
sleeve
5 (44.3)
±10%
1.5–25
(16–4)
Cable
end
sleeve
3.5 (31)
±10%
0.5–4
(20–12)
Cable
end
sleeve
0.8 (7.1)
±10%
M8
10 (88.5)
±10%
77
87
109
128
77
87
109
128
X6
2.5–95
(14–3/0)
Cable lug
M8
10 (88.5)
±10%
1.5–50
(16–
1-1/0)
Cable
end
sleeve
4 (35.4)
±10%
0.5–4
(20–12)
Cable
end
sleeve
0.8 (7.1)
±10%
M8
10 (88.5)
±10%
155
197
155
197
240
X7
25–300
(4–600)
Cable lug
M16
50
(442.5)
±10%
16–150
(6–300)
Cable
end
sleeve
18
(159.3)
±10%
0.5–4
(20–12)
Cable
end
sleeve
0.8 (7.1)
±10%
M12
40 (354)
±10%
240
296
296
366
395
X8
25–300
(4–600)
Cable lug
M16
50
(442.5)
±10%
16–150
(6–300)
Cable
end
sleeve
18
(159.3)
±10%
0.5–4
(20–12)
Cable
end
sleeve
0.8 (7.1)
±10%
M12
40 (354)
±10%
Table 7.5 Terminal Specications, 600 V, 60 Hz
Specications Design Guide
MG80C502 Danfoss A/S © 10/2016 All rights reserved. 57