21-66 Ext. 3 On Reference Bandwidth
Range: Function:
value of this parameter, the on-
reference status bit is high.
3.20 Parameters: 22-** Application
Functions
This group contains parameters used for monitoring HVAC
applications.
22-00 External Interlock Delay
Range: Function:
0 s* [0 - 600 s] Only relevant if 1 of the digital
inputs in parameter group 5-1*
Digital Inputs has been
programmed for [7] External
Interlock. The external interlock
timer introduces a delay after the
signal has been removed from the
digital input programmed for
external interlock, before reaction
takes place.
22-01 Power Filter Time
Range: Function:
0.50 s* [0.02 - 10 s] Sets the time constant for the
ltered power readout. A higher
value gives a more steady readout
but a slower system response to
changes.