5.1.28 35-** MCB 114 Sensor Input Option
Paramete
r
number
Parameter description Default value 4-set-up Change
during
operation
Conver-
sion index
Type
35-0* Temp. Input Mode
35-00 Term. X48/4 Temperature Unit [60] °C All set-ups TRUE - Uint8
35-01 Term. X48/4 Input Type [0] Not Connected All set-ups TRUE - Uint8
35-02 Term. X48/7 Temperature Unit [60] °C All set-ups TRUE - Uint8
35-03 Term. X48/7 Input Type [0] Not Connected All set-ups TRUE - Uint8
35-04 Term. X48/10 Temperature Unit [60] °C All set-ups TRUE - Uint8
35-05 Term. X48/10 Input Type [0] Not Connected All set-ups TRUE - Uint8
35-06 Temperature Sensor Alarm Function [5] Stop and trip All set-ups TRUE - Uint8
35-1* Temp. Input X48/4
35-14 Term. X48/4 Filter Time Constant 0.005 s All set-ups TRUE -3 Uint16
35-15 Term. X48/4 Temp. Monitor [0] Disabled All set-ups TRUE - Uint8
35-16 Term. X48/4 Low Temp. Limit ExpressionLimit All set-ups TRUE 0 Int16
35-17 Term. X48/4 High Temp. Limit ExpressionLimit All set-ups TRUE 0 Int16
35-2* Temp. Input X48/7
35-24 Term. X48/7 Filter Time Constant 0.005 s All set-ups TRUE -3 Uint16
35-25 Term. X48/7 Temp. Monitor [0] Disabled All set-ups TRUE - Uint8
35-26 Term. X48/7 Low Temp. Limit ExpressionLimit All set-ups TRUE 0 Int16
35-27 Term. X48/7 High Temp. Limit ExpressionLimit All set-ups TRUE 0 Int16
35-3* Temp. Input X48/10
35-34 Term. X48/10 Filter Time Constant 0.005 s All set-ups TRUE -3 Uint16
35-35 Term. X48/10 Temp. Monitor [0] Disabled All set-ups TRUE - Uint8
35-36 Term. X48/10 Low Temp. Limit ExpressionLimit All set-ups TRUE 0 Int16
35-37 Term. X48/10 High Temp. Limit ExpressionLimit All set-ups TRUE 0 Int16
35-4* Analog Input X48/2
35-42 Term. X48/2 Low Current 4 mA All set-ups TRUE -5 Int16
35-43 Term. X48/2 High Current 20 mA All set-ups TRUE -5 Int16
35-44 Term. X48/2 Low Ref./Feedb. Value 0 N/A All set-ups TRUE -3 Int32
35-45 Term. X48/2 High Ref./Feedb. Value 100 N/A All set-ups TRUE -3 Int32
35-46 Term. X48/2 Filter Time Constant 0.005 s All set-ups TRUE -3 Uint16
35-47 Term. X48/2 Live Zero [1] Enabled All set-ups TRUE - Uint8
Parameter Lists
VLT
®
HVAC Drive FC 102
314 Danfoss A/S © 10/2019 All rights reserved. M0010001