EasyManuals Logo
Home>Danfoss>DC Drives>vlt FC 102

Danfoss vlt FC 102 Programming Guide

Danfoss vlt FC 102
322 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #205 background imageLoading...
Page #205 background image
22-32 Low Speed [RPM]
Range: Function:
Size
related*
[ 0 - par.
22-36 RPM]
To be used if parameter 0-02 Motor
Speed Unit is set to [0] RPM
(parameter not visible if [1] Hz is
selected).
Set used speed for the 50% level.
This function is used for storing
values necessary for tuning no-ow
detection.
22-33 Low Speed [Hz]
Range: Function:
Size
related*
[ 0 - par.
22-37 Hz]
To be used if parameter 0-02 Motor
Speed Unit is set for [1] Hz
(parameter not visible if [0] RPM is
selected).
Set used speed for the 50% level.
The function is used for storing
values necessary for tuning no-ow
detection.
22-34 Low Speed Power [kW]
Range: Function:
Size
related*
[ 0 - 5.50 kW] To be used if
parameter 0-03 Regional Settings is
set for [0] International (parameter
not visible if [1] North America is
selected).
Set power consumption at 50%
speed level.
This function is used for storing
values necessary for tuning no-ow
detection.
22-35 Low Speed Power [HP]
Range: Function:
Size
related*
[ 0 - 7.50 hp] To be used if
parameter 0-03 Regional Settings is
set for [1] North America (parameter
not visible if [0] International is
selected).
Set power consumption at 50%
speed level.
This function is used for storing
values necessary for tuning no-ow
detection.
22-36 High Speed [RPM]
Range: Function:
Size
related*
[ 0 - par. 4-13
RPM]
To be used if parameter 0-02 Motor
Speed Unit is set for [0] RPM
(parameter not visible if [1] Hz is
selected).
Set used speed for the 85% level.
22-36 High Speed [RPM]
Range: Function:
The function is used for storing
values necessary for tuning no-ow
detection.
22-37 High Speed [Hz]
Range: Function:
Size
related*
[ 0 - par. 4-14
Hz]
To be used if parameter 0-02 Motor
Speed Unit is set for [1] Hz
(parameter not visible if [0] RPM is
selected).
Set used speed for the 85% level.
The function is used for storing
values necessary for tuning no-ow
detection.
22-38 High Speed Power [kW]
Range: Function:
Size
related*
[ 0 - 5.50 kW] To be used, if
parameter 0-03 Regional Settings is
set for [0] International (parameter
not visible if [1] North America is
selected).
Set power consumption at 85%
speed level.
This function is used for storing
values necessary for tuning no-ow
detection.
22-39 High Speed Power [HP]
Range: Function:
Size
related*
[ 0 - 7.50 hp] To be used if
parameter 0-03 Regional Settings is
set for [1] North America (parameter
not visible if [0] International is
selected).
Set power consumption at 85%
speed level.
This function is used for storing
values necessary for tuning no-ow
detection.
Parameter Descriptions Programming Guide
M0010001 Danfoss A/S © 10/2019 All rights reserved. 203
3 3

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals