22-32 Low Speed [RPM]
Range: Function:
Size
related*
[ 0 - par.
22-36 RPM]
To be used if parameter 0-02 Motor
Speed Unit is set to [0] RPM
(parameter not visible if [1] Hz is
selected).
Set used speed for the 50% level.
This function is used for storing
values necessary for tuning no-ow
detection.
22-33 Low Speed [Hz]
Range: Function:
Size
related*
[ 0 - par.
22-37 Hz]
To be used if parameter 0-02 Motor
Speed Unit is set for [1] Hz
(parameter not visible if [0] RPM is
selected).
Set used speed for the 50% level.
The function is used for storing
values necessary for tuning no-ow
detection.
22-34 Low Speed Power [kW]
Range: Function:
Size
related*
[ 0 - 5.50 kW] To be used if
parameter 0-03 Regional Settings is
set for [0] International (parameter
not visible if [1] North America is
selected).
Set power consumption at 50%
speed level.
This function is used for storing
values necessary for tuning no-ow
detection.
22-35 Low Speed Power [HP]
Range: Function:
Size
related*
[ 0 - 7.50 hp] To be used if
parameter 0-03 Regional Settings is
set for [1] North America (parameter
not visible if [0] International is
selected).
Set power consumption at 50%
speed level.
This function is used for storing
values necessary for tuning no-ow
detection.
22-36 High Speed [RPM]
Range: Function:
Size
related*
[ 0 - par. 4-13
RPM]
To be used if parameter 0-02 Motor
Speed Unit is set for [0] RPM
(parameter not visible if [1] Hz is
selected).
Set used speed for the 85% level.
22-36 High Speed [RPM]
Range: Function:
The function is used for storing
values necessary for tuning no-ow
detection.
22-37 High Speed [Hz]
Range: Function:
Size
related*
[ 0 - par. 4-14
Hz]
To be used if parameter 0-02 Motor
Speed Unit is set for [1] Hz
(parameter not visible if [0] RPM is
selected).
Set used speed for the 85% level.
The function is used for storing
values necessary for tuning no-ow
detection.
22-38 High Speed Power [kW]
Range: Function:
Size
related*
[ 0 - 5.50 kW] To be used, if
parameter 0-03 Regional Settings is
set for [0] International (parameter
not visible if [1] North America is
selected).
Set power consumption at 85%
speed level.
This function is used for storing
values necessary for tuning no-ow
detection.
22-39 High Speed Power [HP]
Range: Function:
Size
related*
[ 0 - 7.50 hp] To be used if
parameter 0-03 Regional Settings is
set for [1] North America (parameter
not visible if [0] International is
selected).
Set power consumption at 85%
speed level.
This function is used for storing
values necessary for tuning no-ow
detection.
Parameter Descriptions Programming Guide
M0010001 Danfoss A/S © 10/2019 All rights reserved. 203