ramps up again and the pressure reaches the set value
(P
set
).
External PID
controller
FC
130BA256.11
P
P
System
P
Set
f
Out
f
Ref
Illustration 3.59 Boost System
2) In systems where the pressure or temperature is
controlled by an external PI controller, the wake-up
conditions cannot be based on feedback from the
pressure/temperature transducer as the setpoint is not
known. In the example with a boost system, the desired
pressure P
set
is not known. Set parameter 1-00 Congu-
ration Mode to [0] Open Loop.
Example: Boost system.
130BA258.10
t
1
p
(Pressure)
Time
Time
No/Low Flow
detected
p
System
P
Set
Sleep mode
activated
P
Ref
= P
Wake
(Frequency)
f
Ref
f
Ref /
f
Out
f
Ref
f
Out
f
Wake
f
Out
Illustration 3.60 Boost System
When low power or low speed is detected, the motor is
stopped, but the reference signal (f
ref
) from the external
controller is still monitored. Because of the low pressure
created, the controller increases the reference signal to
gain pressure. When the reference signal has reached a set
value, f
wake
, the motor restarts.
The speed is set manually by an external reference signal
(remote reference). Use default settings (parameter group
22-3* No-Flow Power Tuning) for tuning of the no-ow
function.
Internal PI controller
(parameter 1-00 Conguration Mode: Closed loop)
External PI controller or manual control
(parameter 1-00 Conguration Mode: Open loop)
Sleep mode Wake up Sleep mode Wake up
No-ow detection (pumps only) Yes Yes (except manual
setting of speed)
Low speed detection Yes Yes
External signal Yes Yes
Pressure/temperature
(transmitter connected)
Yes No
Output frequency No Yes
Table 3.26 Conguration Overview
NOTICE
Sleep mode is not active when local reference is active
(press the navigation keys to set speed manually). See
parameter 3-13 Reference Site.
Does not work in hand-on mode. Carry out auto set-up
in open loop before setting input/output in closed loop.
22-40 Minimum Run Time
Range: Function:
10 s* [0 - 600 s] Set the minimum running time for
the motor after a start command
(digital input or eldbus) before
entering sleep mode.
Parameter Descriptions Programming Guide
M0010001 Danfoss A/S © 10/2019 All rights reserved. 205
3 3

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
BrandDanfoss
Modelvlt FC 102
CategoryDC Drives
LanguageEnglish

Related product manuals