Warranty-aecting alarms (see parameter 24-09 Fire Mode Alarm Handling)
•
Fire mode activated
•
Fire mode deactivated
All critical alarms occurring while re mode is activated are logged as usual.
NOTICE
During re mode-operation, all stop commands to the frequency converter are ignored, including coast/coast inverse
and external interlock. However, if Safe Torque O is available in the frequency converter, this function is still active.
NOTICE
If using the live zero-function in re mode, then it is also active for analog inputs other than that used for re mode
setpoint/feedback. Should the feedback to any of those other analog inputs be lost, for example a cable is burned, live
zero-function operates. If this is not wanted, disable the live zero-function for those other inputs.
Set the wanted live zero-function in case of a missing signal when re mode active in parameter 6-02 Fire Mode Live
Zero Timeout Function.
Warning for live zero has a higher priority than the warning Fire Mode.
NOTICE
If setting the command [11] Start Reversing on a digital input terminal in parameter 5-10 Terminal 18 Digital Input, the
frequency convertor understands this as a reversing command.
24-00 Fire Mode Function
Option: Function:
NOTICE
Alarms are produced or
ignored in accordance with the
selection in
parameter 24-09 Fire Mode
Alarm Handling.
[0] * Disabled Fire mode-function is not active.
[1] Enabled-Run
Forward
In this mode, the motor continues
to operate in a clockwise direction.
Works only in open loop. Set
parameter 24-01 Fire Mode Congu-
ration to [0] Open Loop.
[2] Enabled-Run
Reverse
In this mode, the motor continues
to operate in a counterclockwise
direction. Works only in open loop.
Set parameter 24-01 Fire Mode
Conguration to [0] Open Loop.
[3] Enabled-Coast In this mode, the output is
disabled, and the motor is allowed
to coast to stop.
[4] Enabled-Run
Fwd/Rev
Parameter Descriptions
VLT
®
HVAC Drive FC 102