EasyManuals Logo

Danfoss vlt FC 102 Programming Guide

Danfoss vlt FC 102
322 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #278 background imageLoading...
Page #278 background image
No. Description Warning Alarm/
trip
Alarm/
trip lock
Parameter
reference
Fire mode alarm handling selected
in parameter 24-09 Fire Mode Alarm
Handling
Critical alarms cause a trip.
Warranty-
aecting
alarms
in re
mode
48 1.8 V supply low (X) (X)
Parameter 14-90
Fault Settings
Ignored Ignored
(Trip / Trip
lock)
49 Speed limit X (X)
Parameter 1-86
Trip Speed Low [RPM]
Ignored Ignored
Warning /
(Trip)
50
AMA calibration
failed
X Ignored Ignored Trip
51
AMA check Unom
and Inom
X Ignored Ignored Trip
52 AMA low Inom X Ignored Ignored Trip
53
AMA motor too
big
X Ignored Ignored Trip
54
AMA motor too
small
X Ignored Ignored Trip
55
AMA Parameter
out of range
X Ignored Ignored Trip
56
AMA interrupted
by user
X Ignored Ignored Trip
57 AMA timeout X Ignored Ignored Trip
58 AMA internal fault X X Ignored Ignored Trip
59 Current limit (X)
Parameter 14-90
Fault Settings
Ignored Ignored (Warning)
60 External Interlock X Ignored Ignored Warning
62
Output Frequency
at Maximum Limit
X Ignored Ignored Warning
64 Voltage Limit (X)
Parameter 14-90
Fault Settings
Ignored Ignored (Warning)
65
Control Board Over
temperature
X X (X)
Parameter 14-90
Fault Settings
Ignored Ignored
Warning /
Trip / (Trip
lock)
X
66
Heat sink
Temperature Low
X Ignored Ignored Warning
67
Option Congu-
ration has
Changed
X Ignored Ignored Trip
68 Safe Stop (X)
X
(1)
Parameter 5-19
Terminal 37 Safe Stop
Trip Trip Trip
69 Pwr. Card Temp X (X)
Parameter 14-90
Fault Settings
Ignored Ignored
Trip / (Trip
lock)
X
70
Illegal FC congu-
ration
X Ignored Ignored Trip Lock
71 PTC 1 Safe Stop X
X
(1)
Ignored Ignored
Warning /
Trip
72 Dangerous Failure X1) Ignored Ignored Trip Lock
73
Safe Stop Auto
Restart
(X) (X)
Parameter 5-19
Terminal 37
Safe Stop
Ignored Ignored
(Warning /
Trip)
76 Power Unit Setup X Ignored Ignored Warning
79 Illegal PS cong X X Ignored Ignored
Trip / Trip
lock
Troubleshooting
VLT
®
HVAC Drive FC 102
276 Danfoss A/S © 10/2019 All rights reserved. M0010001
44

Table of Contents

Other manuals for Danfoss vlt FC 102

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt FC 102 and is the answer not in the manual?

Danfoss vlt FC 102 Specifications

General IconGeneral
CategoryDC Drives
ModelDanfoss VLT FC 102
Output voltage range0 to rated motor voltage
Power range0.37 kW to 200 kW
Communication interfacesRS-485
Protection featuresOvervoltage, undervoltage, overcurrent, short circuit, earth fault, overtemperature, motor thermal protection
Cooling methodAir-cooled
Enclosure ratingIP20, IP21, IP55 (depending on model)
ApprovalsCE, UL, cUL

Related product manuals