8.8.2 UL Compliance
1 x 200–240 V
Recommended max. fuse
Power
[kW]
Max. prefuse
size [A]
Buss-
mann
JFHR2
Buss-
mann
RK1
Buss-
mann
J
Buss-
mann
T
Buss-
mann
CC
Buss-
mann
CC
Buss-
mann
CC
SIBA
RK1
Littelfuse
RK1
Ferraz-
Shawmut
CC
Ferraz-
Shawmut
RK1
Ferraz-
Shawmut
J
1.1 15
FWX-1
5
KTN-
R15 JKS-15 JJN-15
FNQ-
R-15
KTK-
R-15
LP-
CC-15
501790
6-016 KLN-R15 ATM-R15 A2K-15R HSJ15
1.5 20
FWX-2
0
KTN-
R20 JKS-20 JJN-20
FNQ-
R-20
KTK-
R-20
LP-
CC-20
501790
6-020 KLN-R20 ATM-R20 A2K-20R HSJ20
2.2 30*
FWX-3
0
KTN-
R30 JKS-30 JJN-30
FNQ-
R-30
KTK-
R-30
LP-
CC-30
501240
6-032 KLN-R30 ATM-R30 A2K-30R HSJ30
3.0 35
FWX-3
5
KTN-
R35 JKS-35 JJN-35 --- KLN-R35 --- A2K-35R HSJ35
3.7 50
FWX-5
0
KTN-
R50 JKS-50 JJN-50
501400
6-050 KLN-R50 --- A2K-50R HSJ50
5.5 60**
FWX-6
0
KTN-
R60 JKS-60 JJN-60
501400
6-063 KLN-R60 --- A2K-60R HSJ60
7.5 80
FWX-8
0
KTN-
R80 JKS-80 JJN-80
501400
6-080 KLN-R80 --- A2K-80R HSJ80
15 150
FWX-1
50
KTN-
R150
JKS-15
0
JJN-15
0
202822
0-150 KLN-R150 A2K-150R HSJ150
22 200
FWX-2
00
KTN-
R200
JKS-20
0
JJN-20
0
202822
0-200 KLN-R200 A2K-200R HSJ200
Table 8.16 1 x 200–240 V
* Siba allowed up to 32 A; ** Siba allowed up to 63 A
3x200–240 V
Recommended max. fuse
Power
[kW]
Bussmann
Type RK1
1)
Bussmann
Type J
Bussmann
Type T
Bussmann
Type CC
Bussmann
Type CC
Bussmann
Type CC
1.1 KTN-R-10 JKS-10 JJN-10 FNQ-R-10 KTK-R-10 LP-CC-10
1.5 KTN-R-15 JKS-15 JJN-15 FNQ-R-15 KTK-R-15 LP-CC-15
2.2 KTN-R-20 JKS-20 JJN-20 FNQ-R-20 KTK-R-20 LP-CC-20
3.0 KTN-R-25 JKS-25 JJN-25 FNQ-R-25 KTK-R-25 LP-CC-25
3.7 KTN-R-30 JKS-30 JJN-30 FNQ-R-30 KTK-R-30 LP-CC-30
5.5 KTN-R-50 KS-50 JJN-50 - - -
7.5 KTN-R-60 JKS-60 JJN-60 - - -
11 KTN-R-80 JKS-80 JJN-80 - - -
15–18.5 KTN-R-125 JKS-125 JJN-125 - - -
22 KTN-R-150 JKS-150 JJN-150 - - -
30 KTN-R-200 JKS-200 JJN-200 - - -
37 KTN-R-250 JKS-250 JJN-250 - - -
Table 8.17 3x200–240 V, Enclosure Types A, B and C
Specifications
VLT
®
HVAC Drive Instruction Manual
72 MG11AJ22 - Rev. 2013-09-13
88