8.4.67 ALARM 70, Illegal FC Configuration
Cause
The control card and power card are incompatible.
Troubleshooting
To check compatibility, contact the Danfoss supplier with the type code from the unit nameplate and the part numbers on the
cards.
8.4.68 ALARM 71, PTC 1 Safe Stop
Cause
Because the motor is too warm, the VLT
®
PTC Thermistor Card MCB 112 activated the Safe Torque Off (STO).
Troubleshooting
Once the motor temperature reaches an acceptable level and the digital input from MCB 112 is deactivated, perform 1 of the
following:
- Send a reset signal via bus or digital I/O.
- Press [Reset].
8.4.69 ALARM 72, Dangerous Failure
Cause
Safe Torque Off (STO) with trip lock.
Troubleshooting
An unexpected combination of STO commands has occurred:
VLT
®
PTC Thermistor Card MCB 112 enables X44/10, but STO is not enabled.
MCB 112 is the only device using STO (specified through selection [4] PTC 1 alarm or [5] PTC 12 warning in parameter 5-19 Terminal
37 Safe Stop). STO is activated, but X44/10 is not activated.
8.4.70 WARNING 73, Safe Stop Auto Restart
Cause
STO activated.
Troubleshooting
With automatic restart enabled, the motor can start when the fault is cleared.
Maintenance, Diagnostics, and
Troubleshooting
Operating Guide | VLT® Refrigeration Drive FC 103
AQ275652766279en-000101 / 130R0707| 117
Danfoss A/S © 2020.01

Table of Contents

Other manuals for Danfoss VLT FC 103

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 103 and is the answer not in the manual?

Danfoss VLT FC 103 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 103
CategoryDC Drives
LanguageEnglish

Related product manuals