7.1.6 Wiring Configuration: Start/Stop
Table 28: Start/Stop Command with Safe Torque Off Option
Parameter
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
Function Setting
Parameter 5-10 Terminal 18 Digital Input [Start]*
Parameter 5-12 Terminal 27 Digital Input [0] No operation
Parameter 5-19 Terminal 37 Safe Stop [1] Safe Stop Alarm
*=Default value
Notes/comments:
If parameter 5-12 Terminal 27 Digital Input is set [0] No operation, a jumper wire to terminal 27 is
not needed.
D IN 37 is an option.
e30bb805.13
Speed
Start/Stop (18)
Illustration 40: Start/Stop Command with Safe Torque Off
Wiring Configuration Examples
Operating Guide | VLT® Refrigeration Drive FC 103
AQ275652766279en-000101 / 130R0707| 83
Danfoss A/S © 2020.01