EasyManua.ls Logo

Danfoss VLT FC 103 - Ambient Conditions; Cable Specifications

Danfoss VLT FC 103
170 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Starting torque (constant torque)
Maximum 110% for 60 s once in 10 minutes.
(1)
Overload torque (constant torque)
Maximum 110% for 60 s once in 10 minutes.
(1)
Torque rise time in FLUX (for 5 kHz fsw) 1 ms
Torque rise time in VVC+ (independent of fsw) 10 ms
1
Percentage relates to the drive's nominal current.
9.4 Ambient Conditions
Enclosure IP20/Chassis, IP21/Type 1, IP54/Type 12
Vibration test (standard/ruggedized) 0.7 g/1.0 g
Relative humidty 5%-95% (IEC 721-3-3; Class 3K3 (non-condensing) during
operation)
Aggressive environment (IEC 60068-2-43) H
2
S test Class Kd
Aggressive gases (IEC 60721-3-3) Class 3C3
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature (at 60 AVM switching mode)
- with derating
Maximum 55° C (131° F)
(1)
- with full output power of typical EFF2 motors (up to 90% output
current)
Maximum 50° C (122° F)
(1)
- at full continuous FC output current
Maximum 45° C (113° F)
(1)
Minimum ambient temperature during full-scale operation 0 °C (32 °F)
Minimum ambient temperature at reduced speed performance -10 °C (14 °F)
Temperature during storage/transport -25 to +65/70 °C (-13 to +149/158 °F)
Maximum altitude above sea level without derating 1000 m (3280 ft)
Maximum altitude above sea level with derating 3000 m (9842 ft)
EMC standards, Emission IEC/EN 61800-3
EMC standards, Immunity IEC/EN 61800-3
Energy efficiency class
IE2
(2)
1
For more information, see the Derating section in the design guide.
2
Determined according to IEC 61800-9-2 (EN 50598-2) at:
Rated load.
90% rated frequency.
Switching frequency factory setting.
Switching pattern factory setting.
9.5 Cable Specifications
Maximum motor cable length, shielded 150 m (492 ft)
Maximum motor cable length, unshielded 300 m (984 ft)
Maximum cross-section to control terminals, rigid wire
1.5 mm
2
/16 AWG
Maximum cross-section to control terminals, flexible cable
1 mm
2
/18 AWG
Specifications
Operating Guide | VLT® Refrigeration Drive FC 103
AQ275652766279en-000101 / 130R0707| 133
Danfoss A/S © 2020.01

Table of Contents

Other manuals for Danfoss VLT FC 103

Related product manuals