FC 103 N355 N400 N450
Efficiency
 (3)
0.98 0.98 0.98
Output frequency [Hz] 0–590 0–590 0–590
Heat sink overtemperature trip [°C (°F)] 110 (230) 110 (230) 110 (230)
Control card overtemperature trip [°C (°F)] 80 (176) 80 (176) 80 (176)
Power card overtemperature trip [°C (°F)] 85 (185) 85 (185) 85 (185)
Fan power card overtemperature trip [°C (°F)] 85 (185) 85 (185) 85 (185)
Active in-rush card overtemperature trip [°C (°F)] 85 (185) 85 (185) 85 (185)
1
For fuse ratings, see 9.7 Fuses.
2
Typical power loss is at normal conditions and expected to be within ±15% (tolerance relates to variety in voltage and cable conditions.) These values are based on a typical motor
efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies for dimensioning of drive cooling. If the switching frequency is higher than the default
setting, the power losses can increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/
vltenergyefficiency. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B each add only 4 W.
3
Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy efficiency class, see 
9.4 Ambient
Conditions. For part load losses, see www.danfoss.com/vltenergyefficiency.
Table 43: Electrical Data, Mains Supply 3x380–480 V AC
FC 103 N500 N560
High/normal overloadHigh overload=150% or 160% torque for a duration of 60 s.
Normal overload=110% torque for a duration of 60 s.
NO NO
Typical shaft output at 400 V [kW] 500 560
Typical shaft output at 460 V [hp] 650 750
Typical shaft output at 480 V [kW] 560 630
Enclosure size E2h/E4h E2h/E4h
Output current (3-phase)
Continuous (at 400 V) [A] 880 990
Intermittent (60 s overload) (at 400 V) [A] 968 1089
Continuous (at 460/480 V) [A] 780 890
Intermittent (60 s overload) (at 460/480 V) [A] 858 979
Continuous kVA (at 400 V) [kVA] 610 686
Continuous kVA (at 460 V) [kVA] 621 709
Continuous kVA (at 480 V) [kVA] 648 740
Maximum input current
Continuous (at 400 V) [A] 848 954
Continuous (at 460/480 V) [A] 752 858
Maximum number and size of cables per phase (E2h)
- Mains and motor without brake [mm
2
 (AWG)]
6x240 (6x500 mcm) 6x240 (6x500 mcm)
- Mains and motor with brake [mm
2
 (AWG)]
5x240 (4x500 mcm) 5x240 (4x500 mcm)
Specifications
Operating Guide  | VLT® Refrigeration Drive FC 103
AQ275652766279en-000101 / 130R0707
128 | Danfoss A/S © 2020.01